Generating Automatic & Diagnostic System
ProductsPower Facility Prevention Diagnosis System
After detecting min PD signal using the UHF sensor and PD diagnosis device that occur during insulation of Power device inside the Distribution Board, the PD signal are analyzed to detect abnormal conditions caused by insulation of power facility (TR, MOF, Cable, etc.) and Monitoring the front Display and Warning to site employee through output point Transmit through Ethernet (TCP/IP) and serial communication (RS485) to high system, Monitoring the abnormalities of distribution board in real time by the employee |
- Communication between high system RS485, TCP/IP each 1Port
- Power : Free Voltage(AC110~220V)
Content |
Spec. |
UHF Sensor | -Type : Stand Alone Type (Inside D/L) |
PD Monitoring Device |
- Power : AC 110 ~ 220V (60Hz), 10W Up down - Frequency : 500 ~ 1,500MHz - Display Status 1) LCD (20*4) : Green 2) LED 3EA : PW (Power), COM (Communication), PD - Service Environment 1) Operation Temp. : -20℃ ~ +70℃ 2) Operation Humidity : 5 ~ 90%RH - Communication : TCP/IP(PC) , RS 485(RTU), Protocol : Modbus - Location : Front or Inside of Distribution Board (Option) - Event : Event (PD signal) Storage function 1,000ea |